EXAMPLE 1-Sealant required for 1,000 ft. of 4" pipe with 3" of insulation.
| Where: | D = 10.75 d = 4.5" t = 3.11" |
N = 2 B = 2 (24" length) |
| Longitudinal Area = | N x t x l = | 2 x 3.11 x 1000 | = 518 sq. ft. |
| 12 | 12 |
| Butt Area = | .7854 (D²-d²) | x | length + l |
| 144 | B |
| = | .7854 [(10.75)² - (4.5)²] | x | 100l | = 260 sq. ft. |
| 144 | 2 |
Example 1 - Total Area = 518 + 260 = 778 sq. ft.
| Gallons at 1/8" = | 778 | = 59.8 |
| 13 |
Allowance for losses, etc. = 59.8 x 1.25 = 75 gallons
EXAMPLE 2- Sealant required for 1,000 ft. of 24" pipe with 3" of insulation.
| Where: | D = 30" d = 24" t = 3.0" |
N = 8 B = 1.5 (18" length) |
| Longitudinal Area = | N x t x l = | 8 x 3 x 1000 | = 2,000 sq. ft. |
| 12 | 12 |
| Butt Area = | .7854 (D²-d²) | x | length + l |
| 144 | B |
| = | .7854 (30² - 24²) | x | 100l | = 1179 sq. ft. |
| 144 | 1.5 |
Example 2 - Total Area = 2,000 + 1,179 = 3,179 sq. ft.
| Gallons at 1/8" = | 3179 | = 245 |
| 13 |
Allowance for losses, etc. = 1.25 x 245 = 306 gallons
EXAMPLE 3
Double layer with sealant between layers, inner
layer dry joints - 6" pipe, 2" inner layer, 3" outer layer,
1000 ft. of pipe. The first step is to get the diameters, thicknesses and
number of sections from the insulation tables.
| Inner Layer | D1 = 10.75" outside diameter d1 = 6.625" inside diameter t1 = 2.03" thickness |
| Outer Layer | D2 = 17.00" outside diameter d2 = 10.75" inside diameter t2 = 3.08" thickness |
Sealant areas to be coated are the inside, longitudinal and butt joint areas of the outer layer.
| Inside of Outer Layer A = | ñ d2 l = | 3.14 x 10.75 x 1000 | = 2,813 sq. ft. |
| 12 | 12 |
| Longitudinal Area = | N x t x l = | 2 x 3.08 x 1000 | = 513 sq. ft. |
| 12 | 12 |
| Butt Area = | .7854 (D2)²-(d2)² | x | length + l |
| 144 | 2 |
| = | .7854 [(17)² - 10.75)²] | x | 100l | = 472 sq. ft. |
| 144 | 2 |
Example 3 - Total Area = 2,813 + 513 + 472 = 3,798 sq. ft.
| Gallons at 1/8" = | 3798 | = 292 |
| 13 |
Allowance for losses, etc. = 1.25 x 292 = 365 gallons
Estimating
Sealants - An Overview
Table
S1: Sealant Estimating - Bead of Caulk
Table
S2: Sealant Estimating - Full Joint
Table
S3: Joint Sealer Required - per Lineal Ft Pipe Insulation in 2
ft Sections
Table
S4: Joint Sealer Required - per Lineal Ft Pipe Insulation in 3
ft Sections
C.A.S.
Index - Several Related Tables
Ph: 800.486.9865 || Or: 419.668.2072 ||
Fax: 419.663.1992
info@ExtolOhio.com || Located at:
208 Republic Street, Norwalk, Ohio 44857