Industrial Insulation
 METRIC CHART

Extol of Ohio, Inc.

info@ExtolOhio.com || 208 Republic St, Norwalk, OH 44857
Ph: 800.486.9865 || Or: 419.668.2072 || Fx: 419.663.1992

STEEL PIPE DATA - METRIC
U.S. Nom. Size,
in.
Nom. Size,
mm.
Schedule* Wall Thkns
t, mm
Inside Diam.
d, in.
Surface Area Cross Section Mass Working Pressure***
ASTM A53 B to 200°
Outside,
m²/m
Inside,
m²/m
Metal Area,
mm²
Flow Area,
mm²
Pipe,
kg/m
Water,
kg/m
Mfr.
Process
Joint
Type**
kPa
(gage)
1/4 8 40ST 2.24 9.25 0.043 0.029 80.6 67.1 0.631 0.067 CW T 1296
80XS 3.02 7.67 0.043 0.024 101.5 46.2 0.796 0.046 CW T 6006
3/8 10 40ST 2.31 12.52 0.054 0.039 107.7 123.2 0.844 0.123 CW T 1400
80XS 3.20 10.74 0.054 0.034 140.2 90.7 1.098 0.091 CW T 5654
1/2 15 40ST 2.77 15.80 0.067 0.050 161.5 196.0 1.265 0.196 CW T 1476
80XS 3.73 13.87 0.067 0.044 206.5 151.1 1.618 0.151 CW T 5192
3/4 20 40ST 2.87 20.93 0.084 0.066 214.6 344.0 1.68 0.344 CW T 1496
80XS 3.91 18.85 0.084 0.059 279.7 279.0 2.19 0.279 CW T 4695
1 25 40ST 3.38 26.64 0.105 0.084 318.6 557.6 2.50 0.558 CW T 1558
80XS 4.55 24.31 0.105 0.076 412.1 464.1 3.23 0.464 CW T 4427
1-1/4 32 40ST 3.56 35.05 0.132 0.110 431.3 965.0 3.38 0.965 CW T 1579
80XS 4.85 32.46 0.132 0.102 568.7 827.6 4.45 0.828 CW T 4096
1-1/2 40 40ST 3.68 40.89 0.152 0.128 515.5 1313 4.05 1.313 CW T 1593
80XS 5.08 38.10 0.152 0.120 689.0 1140 5.40 1.140 CW T 3972
2 50 40ST 3.91 52.50 0.190 0.165 690.3 2165 5.43 2.165 CW T 1586
80XS 5.54 49.25 0.190 0.155 953 1905 7.47 1.905 CW T 3799
2-1/2 65 40ST 5.16 62.71 0.229 0.197 1099 3089 8.62 3.089 CW W 3675
80XS 7.01 59.00 0.229 0.185 1454 2734 11.40 2.734 CW W 5757
3 80 40ST 5.49 77.93 0.279 0.245 1438 4769 11.27 4.769 CW W 3323
80XS 7.62 73.66 0.279 0.231 1946 4261 15.25 4.261 CW W 5288
4 100 40ST 6.02 102.26 0.359 0.321 2048 8213 16.04 8.213 CW W 2965
80XS 8.56 97.18 0.359 0.305 2844 7417 22.28 7.417 CW W 4792
6 150 40ST 7.11 154.05 0.529 0.484 3601 18639 28.22 18.64 ERW W 4799
80XS 10.97 146.33 0.529 0.460 5423 16817 42.49 16.82 ERW W 8336
8 200 30 7.04 205.0 0.688 0.644 4687 33000 36.73 33.01 ERW W 3627
40ST 8.18 202.7 0.688 0.637 5419 32280 42.46 32.28 ERW W 4433
80XS 12.70 193.7 0.688 0.608 8234 29460 64.51 29.46 ERW W 7626
10 250 30 7.80 257.5 0.858 0.809 6498 52060 50.91 52.06 ERW W 3344
40ST 9.27 254.5 0.858 0.800 7683 50870 60.20 50.87 ERW W 4178
    XS 12.70 247.7 0.858 0.778 10388 48170 81.39 48.17 ERW W 6116
80 15.06 242.9 0.858 0.763 12208 46350 95.66 46.35 ERW W 7453
12 300 30 8.38 307.1 1.017 0.965 8307 74060 65.09 74.06 ERW W 3096
    ST 9.53 304.8 1.017 0.958 9406 72970 73.70 72.97 ERW W 3641
40 10.31 303.2 1.017 0.953 10158 72190 79.59 72.21 ERW W 4020
    XS 12.70 298.5 1.017 0.938 12414 69940 97.28 69.96 ERW W 5157
80 17.45 289.0 1.017 0.908 16797 65550 131.62 65.57 ERW W 7419
14 350 30ST 9.53 336.6 1.117 1.057 10356 88970 81.15 88.96 ERW W 3316
40 11.10 333.4 1.117 1.047 12013 87290 94.13 87.30 ERW W 3999
     XS 12.70 330.2 1.117 1.037 13681 85610 107.21 85.63 ERW W 4695
80 19.05 317.5 1.117 0.997 20142 79160 157.82 79.17 ERW W 7453
16 400 30ST 9.53 387.4 1.277 1.217 11876 117800 93.06 117.8 ERW W 2903
40XS 12.70 381.0 1.277 1.197 15708 114000 123.09 114.0 ERW W 4109
18 450     ST 9.53 438.2 1.436 1.376 13396 150800 104.98 150.8 ERW W 2579
30 11.10 435.0 1.436 1.367 15556 148600 121.90 148.6 ERW W 3110
    XS 12.70 431.8 1.436 1.357 17735 146450 138.97 146.4 ERW W 3654
40 14.27 428.7 1.436 1.347 19863 144300 155.65 144.3 ERW W 4185
20 500 20ST 9.53 489.0 1.596 1.536 14916 187700 116.88 187.4 ERW W 2324
30XS 12.70 482.6 1.596 1.516 19762 182900 154.85 182.9 ERW W 3289
40 15.06 477.9 1.596 1.501 23325 179400 182.78 179.4 ERW W 4006

Notes:
*Numbers are schedule numbers per ASME Standard B36. 10M; ST=Extra Strong
**T=Thread; W=Weld
***Working pressures were calculated per ASME B31.9 using furnace butt-weld (continuous weld, CW) pipe through 100 mm and electric resistance weld (ERW) thereafter. The allowance A has been taken as:
1)12.5% of t for mill tolerance on pipe wall thickness, plus
2)An arbitrary corrosion allowance of 0.64 mm for pipe sizes through NPS 2 and 1.65 mm from NPS 2½ through 20, plus
3) A thread cutting allowance for sizes through NPS 2

Because the pipe wall thickness of threaded standard pipe is so small after deducting the allowance A, the mechanical strength of the pipe is impaired. It is good practice to limit standard threaded pipe pressure to 620 kPa (gage) for steam and 860 kPa (gage) for water.


Insulation IndustryEXTOL INSULATION SYSTEMS:

COMPLETE PRODUCT LINE
   COMPOSITE INSULATIONS
   CONTOURED HEAD SYSTEMS
   EXCEL-LAP SYSTEMS
   ISOWRAP® PRECISION CUT
   TRACED LINE SYSTEMS
   VALVE & JACKET SYSTEMS

Insulation IndustryDATA SECTIONS:

DESIGN & INSTALLATION TIPS
ESTIMATING TIPS / & CHARTS
EXTOL SYSTEMS DATA
MSDS LISTED BY MANUFACTURER
MSDS LISTED BY PRODUCT TYPE
PRODUCT DATA SHEETS
PUBLICATIONS & ARTICLES
HELPFUL SALES/TRAVEL INFO
WBE CERTIFICATIONS
Insulation Industry BACK TO MAIN

OBTAIN A QUOTE
SURPLUS MATERIAL
PLACE AN ORDER
EMPLOYMENT OPPORTUNITIES

Insulation Industry PASSKEY SECTION:
WAIVER / PASSKEY REQUEST
INSULATION SPECIFICATIONS
DETAILED DRAWINGS_COLD/HOT

Ph: 800.486.9865 || Or: 419.668.2072 || Fax: 419.663.1992
info@ExtolOhio.com || Located at:
208 Republic Street, Norwalk, Ohio 44857