SUCTION, DISCHARGE, AND LIQUID LINE CAPACITIES IN KILOWATTS FOR REFRIGERANT 22 (SINGLE- OR HIGH- STAGE APPLICATIONS)
NOMINAL
LINE SIZE,
mm
SUCTION LINES (Triangle Symbol t = 0.04 K/m) DISCHARGE LINES
(Triangle Symbol t= 0.02 K/m, Triangle Symbol p=74.90)
LIQUID LINES*
SATURATED SUCTION TEMPERATURE, °C
-40 -30 -20 -5 +5 SATURATED SUCTION
TEMPERATURE, °C
VEL. =
0.5 m/s
Triangle Symbol t = 0.02 K/m
Triangle Symbol p = 749 Pa/m
CORRESPONDING Triangle Symbolp, Pa/m
196 277 378 572 731 -40 -20 +5
COPPER LINE
12 0.32 0.50 0.75 1.28 1.76 2.30 2.44 2.60 7.08 11.24
15 0.61 0.95 1.43 2.45 3.37 4.37 4.65 4.95 11.49 21.54
18 1.06 1.66 2.49 4.26 5.85 7.59 8.06 8.59 17.41 37.49
22 1.88 2.93 4.39 7.51 10.31 13.32 14.15 15.07 26.66 66.18
x
28 3.73 5.82 8.71 14.83 20.34 26.24 27.89 29.70 44.57 131.0
35 6.87 10.70 15.99 27.22 37.31 48.03 51.05 54.37 70.52 240.7
42 11.44 17.80 26.56 45.17 61.84 79.50 84.52 90.00 103.4 399.3
54 22.81 35.49 52.81 89.69 122.7 157.3 167.2 178.1 174.1 794.2
X
67 40.81 63.34 94.08 159.5 218.3 279.4 297.0 316.3 269.9 1415.0
79 63.34 98.13 145.9 247.2 337.9 431.3 458.5 488.2 376.5 2190.9
105 136.0 210.3 312.2 527.8 721.9 919.7 977.6 1041.0 672.0 4697.0

Notes:

  1. Table capacities are in kilowatts of refrigeration.
    triangle p = pressure drop per unit equivalent length of line, Pa/m
    triangle t = corresponding change in saturation temperature, K/m
  2. Line capacity for other saturation temperature Triangle Symbol t and equivalent lengths Le
    Line Capacity = Table Capacity [ Table Le X Actual Triangle Symbol t ] 0.55
    _____ _____
    Actual Le Table Triangle Symbol t
  3. Saturation temperature Triangle Symbol t for other capacities and equivalent lengths
    Triangle Symbol t Table Triangle Symbol t [ Actual Le X Actual Capacity ] 1.8
    _____ _____
    Table Le Table capacity
  4. Values in the table at the right are based on 40°C condensing temperature. Multiply table capacities by the following factors for other condensing temperatures.
Condensing
Temperature, °C
Suction
Line
Discharge
Line
80 1.11 0.79
90 1.07 0.88
100 1.03 0.95
110 0.97 1.04
120 0.90 1.10
130 0.86 1.18
140 0.80 1.26

Insulation IndustryEXTOL INSULATION SYSTEMS:

COMPLETE PRODUCT LINE
   COMPOSITE INSULATIONS
   CONTOURED HEAD SYSTEMS
   EXCEL-LAP SYSTEMS
   ISOWRAP® PRECISION CUT
   TRACED LINE SYSTEMS
   VALVE & JACKET SYSTEMS

Insulation IndustryDATA SECTIONS:

DESIGN & INSTALLATION TIPS
ESTIMATING TIPS / & CHARTS
EXTOL SYSTEMS DATA
MSDS LISTED BY MANUFACTURER
MSDS LISTED BY PRODUCT TYPE
PRODUCT DATA SHEETS
PUBLICATIONS & ARTICLES
HELPFUL SALES/TRAVEL INFO
WBE CERTIFICATIONS
Insulation Industry BACK TO MAIN

OBTAIN A QUOTE
SURPLUS MATERIAL
PLACE AN ORDER
EMPLOYMENT OPPORTUNITIES

Insulation Industry PASSKEY SECTION:
WAIVER / PASSKEY REQUEST
INSULATION SPECIFICATIONS
DETAILED DRAWINGS_COLD/HOT

Ph: 800.486.9865 || Or: 419.668.2072 || Fax: 419.663.1992
info@ExtolOhio.com || Located at:
208 Republic Street, Norwalk, Ohio 44857