SUCTION, DISCHARGE, AND LIQUID LINE CAPACITIES IN TONS FOR REFRIGERANT 134a
(SINGLE- OR HIGH-STAGE APPLICATIONS) |
| LINE SIZE |
SUCTION LINES (
t = 2°F) |
DISCHARGE LINES
(
t= 1°F,
p= 2.2 psi/100 ft) |
LINE
SIZE |
LIQUID LINES |
| SATURATED SUCTION TEMPERATURE, °F |
SEE NOTES a AND b |
TYPE L
COPPER,
OD |
0 |
10 |
20 |
30 |
40 |
SATURATED SUCTION
TEMPERATURE, °F |
TYPE L
COPPER,
OD |
VEL. =
100 fpm |
t = 1°F
p = 2.2 psi |
CORRESPONDING
p, psi/100 ft |
| 1.00 |
1.19 |
1.41 |
1.66 |
1.93 |
0 |
20 |
40 |
| 1/2 |
0.14 |
0.18 |
0.23 |
0.29 |
0.35 |
0.54 |
0.57 |
0.59 |
1/2 |
2.13 |
2.79 |
| 5/8 |
0.27 |
0.34 |
0.43 |
0.54 |
0.66 |
1.01 |
1.07 |
1.12 |
5/8 |
3.42 |
5.27 |
| 7/8 |
0.71 |
0.91 |
1.14 |
1.42 |
1.75 |
2.67 |
2.81 |
2.94 |
7/8 |
7.09 |
14.00 |
| 1-1/8 |
1.45 |
1.84 |
2.32 |
2.88 |
3.54 |
5.40 |
5.68 |
5.95 |
1-1/8 |
12.10 |
28.40 |
| 1-3/8 |
2.53 |
3.22 |
4.04 |
5.02 |
6.17 |
9.42 |
9.91 |
10.40 |
1-3/8 |
18.40 |
50. 00 |
| 1-5/8 |
4.02 |
5.10 |
6.39 |
7.94 |
9.77 |
14.90 |
15.70 |
16.40 |
1-5/8 |
26.10 |
78.60 |
| 2-1/8 |
8.34 |
10.60 |
13.30 |
16.50 |
20.20 |
30.80 |
32.40 |
34.00 |
2-1/8 |
45.30 |
163.00 |
| 2-5/8 |
14.80 |
18.80 |
23.50 |
29.10 |
35.80 |
54.40 |
57.20 |
59.90 |
2-5/8 |
69.90 |
290.00 |
| 3-1/8 |
23.70 |
30.00 |
37.50 |
46.40 |
57.10 |
86.70 |
91.20 |
95.50 |
3-1/8 |
100.00 |
462.00 |
| 3-5/8 |
35.10 |
44.60 |
55.80 |
69.10 |
84.80 |
129.00 |
135.00 |
142.00 |
3-5/8 |
135.00 |
688.00 |
| 4-1/8 |
49.60 |
62.90 |
78.70 |
97.40 |
119.43 |
181.00 |
191.00 |
200.00 |
4-1/8 |
175.00 |
971.00 |
| 5-1/8 |
88.90 |
113.00 |
141.00 |
174.00 |
213.00 |
323.00 |
340.00 |
356.00 |
5-1/8 |
3.42 |
5.27 |
| 6-1/8 |
143.00 |
181.00 |
226.00 |
280.00 |
342.00 |
518.00 |
545.00 |
571.00 |
6-1/8 |
7.09 |
14.00 |
a The sizing shown is recommended where any gas generated in the receiver must return up the condensate line to the condenser without restricting condensate flow. Water-cooled condensers, where the receiver ambient temperature may be higher than the refrigerant condensing temperature, fall into this category.
b The line pressure drop
p is conservative; if subcooling is substantial or the line is short, a smaller size line may be used. Applications with very little subcooling or very long lines may require a larger line.
|
|
|