Extol Ohio
Extol Ohio
Register     Sign In     Sitemap     HomeExtol Ohio
 Home  |   Line Card   |   Mechanical Joints   |   Metal Fab   |   OEM Products   |   Preformed Heads   |   Valve Insulation
Extol Ohio
Extol Ohio
Extol Ohio
 

Specs by Mfg.
View Extol Products
Request a Sample
 
 
 
 
 
 
Contact Us

Extol of Ohio
208 Republic Street
Norwalk, OH 44857
800.486.9865
419.668.2072
Fax 419.663.1992
 
   
Home  >>  Useful Charts  >  Refrigerant-134a-Capacities
Extol Ohio
SUCTION, DISCHARGE, AND LIQUID LINE CAPACITIES IN TONS FOR REFRIGERANT 134a
(SINGLE- OR HIGH-STAGE APPLICATIONS)
LINE SIZE SUCTION LINES ( Triangle Symbol t = 2°F) DISCHARGE LINES
( Triangle Symbol t= 1°F, Triangle Symbol p= 2.2 psi/100 ft)
LINE
SIZE
LIQUID LINES
SATURATED SUCTION TEMPERATURE, °F SEE NOTES a AND b
TYPE L
COPPER,
OD
0 10 20 30 40 SATURATED SUCTION
TEMPERATURE, °F
TYPE L
COPPER,
OD
VEL. =
100 fpm
Triangle Symbol t = 1°F
Triangle Symbol p = 2.2 psi
CORRESPONDING Triangle Symbol p, psi/100 ft
1.00 1.19 1.41 1.66 1.93 0 20 40
1/2 0.14 0.18 0.23 0.29 0.35 0.54 0.57 0.59 1/2 2.13 2.79
5/8 0.27 0.34 0.43 0.54 0.66 1.01 1.07 1.12 5/8 3.42 5.27
7/8 0.71 0.91 1.14 1.42 1.75 2.67 2.81 2.94 7/8 7.09 14.00
1-1/8 1.45 1.84 2.32 2.88 3.54 5.40 5.68 5.95 1-1/8 12.10 28.40
1-3/8 2.53 3.22 4.04 5.02 6.17 9.42 9.91 10.40 1-3/8 18.40 50. 00
1-5/8 4.02 5.10 6.39 7.94 9.77 14.90 15.70 16.40 1-5/8 26.10 78.60
2-1/8 8.34 10.60 13.30 16.50 20.20 30.80 32.40 34.00 2-1/8 45.30 163.00
2-5/8 14.80 18.80 23.50 29.10 35.80 54.40 57.20 59.90 2-5/8 69.90 290.00
3-1/8 23.70 30.00 37.50 46.40 57.10 86.70 91.20 95.50 3-1/8 100.00 462.00
3-5/8 35.10 44.60 55.80 69.10 84.80 129.00 135.00 142.00 3-5/8 135.00 688.00
4-1/8 49.60 62.90 78.70 97.40 119.43 181.00 191.00 200.00 4-1/8 175.00 971.00
5-1/8 88.90 113.00 141.00 174.00 213.00 323.00 340.00 356.00 5-1/8 3.42 5.27
6-1/8 143.00 181.00 226.00 280.00 342.00 518.00 545.00 571.00 6-1/8 7.09 14.00

Notes:

  1. Table capacities are in tons of refrigeration.
    Triangle Symbol p = pressure drop due to line friction, psi per 100 ft of equivalent line length
    Triangle Symbol t = corresponding change in saturation temperature °F per 100 ft
  2. Line capacity for other saturation temperature Triangle Symbol t and equivalent lengths Le
    Line Capacity = Table Capacity [ Table Le X Actual Triangle Symbol t ] 0.55
    _____ _____
    Actual L Table Triangle Symbol t
  3. Saturation temperature Triangle Symbol t for other capacities and equivalent lengths
    Triangle Symbol t Table Triangle Symbol t [ Table Le X Actual Capacity ] 1.8
    _____ _____
    Actual Le Table capacity
  4. Values in the table at the right are based on 105°F condensing temperature. Multiply table capacities by the following factors for other condensing temperatures.
Condensing
Temperature, °F
Suction
Line
Discharge Line
80 1.158 0.804
90 1.095 0.882
100 1.032 0.961
110 0.968 1.026
120 0.902 1.078
130 0.902 1.156
 

a The sizing shown is recommended where any gas generated in the receiver must return up the condensate line to the condenser without restricting condensate flow. Water-cooled condensers, where the receiver ambient temperature may be higher than the refrigerant condensing temperature, fall into this category.

b The line pressure drop Triangle Symbol p is conservative; if subcooling is substantial or the line is short, a smaller size line may be used. Applications with very little subcooling or very long lines may require a larger line.

  

 Home  |   Line Card   |   Mechanical Joints   |   Metal Fab   |   OEM Products   |   Preformed Heads   |   Valve Insulation

Extol OhioPrivacy Policy  |  Terms and Conditions
Website created and maintained by WSI Copyright © 2010 All Rights Reserved.